“Cair” offers I/P Transducers (converter)
Manufacturer: CAIR euromatiic
0
Applications
The Cair 500 IP series transducers converts electrical signal to a pneumatic output which can be used to operate the followings:
Valve, Valve-Actuators
Damper and Louver Actuators
Valve Positioners
Air-Cylinders
Relays
Clutches
Web Tensioners and Brakes
   
Used in:
Petrochemical Processing Systems
Energy Management
HVAC Systems
Textile Processing Systems
Pharmaceutical Processing System
Pulp and Handling Controls
 
Specifications Low Output Range (up to 30 psig) High Output Range (up to 120 psig)
Supply Pressure Range (Min./Max.) Minimum - 21 kPa(3psig) above maximum output Maximum - 700 kPa (100 psig) Minimum = 35 kpa (5psig) above maximum output 
Maximum - 1050 kPa (150 psig)
Supply Pressure Sensitivity ±   0.15%   of span per 10kpa (±  0.1 % of span per psig at mid range) ± .005% of span per 7.0 kpa (1.0 psig)
Terminal Based ± 1.0% of Span  ± 1.5% of span typical ± 2.0%max.
Linearity ±  0.5% of span  ± 1.0% of span
Repeatability ±   1.0% of Span ± 1.0% of span
Hysteresis Response Time Depends on pressure range typ. less than 0.25 sec. for 3-15 psig units Depends on pressure range - typ.
Flow Rate 7.6m3/hr(4.5 SCFM) at *175kpa(25psig) supply 20.0m3/hr (12.0 SCFM) at 700 kpa (100 psig) supply 40.8m3/hr(24.0 SCFM) at 1050 pa (150 psig) supply
Relief Capacity 3.4 m3/hr(2SCFM) at 35 kpa (5psig)above 140 kpa (20 psig) 
set point
11.9m3/hr(7SCFM) at 35kpa (10psig) above 140 kpa (20 psig) set point
Maximum Air Consumption Media  0.3m3/hr(0.15 SCFM) at midrange typical Oil free, clean dry air filtered to 40 microns. 0.15 m3/hr (0.08 SCFM) at midrange typ.
Temp. Range (Operating) -30°C to 60°C(-20°F to 140°F)  
Port Sizes 1/4" NPT (Pneumatic) DIN 43650 connector (Electric) 1/4" NPT (Pneumatic) DIN-43650 connector (Electric)
Weight 2.2 Ibs. (1.0kg) approx. 2.2 lbs.(1.0kg) approx
 
IP 501     I/P Transducers 500IP
Output Range
Part No. Input psi kpa lmpedance±1%
IP 501 4-20 mADC 3-15 20-100 200Ώ
IP 502 4-20 mADC 9-15 60-100 110Ώ
IP 503 4-20 mADC 3-9 20-60 110Ώ
IP 504 4-20 mADC 3-27 20-185 240Ώ
IP 505 4-20 mADC 6-30 40-200 240Ώ
IP 506 4-20 mADC 1-17 7-117 270Ώ
IP 507 10-50 mADC 3-15 20-100 90Ώ
IP 508 10-50 mADC 3-27 20-185 105Ώ
IP 509 10-50 mADC 6-30 40-200 105Ώ
IP 510 4-20 mADC 2-60* 14-420 245Ώ
IP 511   3-120* 20-830 280Ώ
IP 512 0-60 mADC 2-120* 15-830 240Ώ
E/P Transducers 500 IP   
IP 513 0-5VDC 3-15 20-100 625Ώ
IP 514 0-5VDC 3-17 20-185 550Ώ
IP 515 0-5VDC 6-30 40-200 560Ώ
IP 516 1 -9VDC 3-15 20-100 1010Ώ
IP 517 1 -9VDC 3-27 20-185 860Ώ
IP 518 1 -9VDC 6-30 40-200 860Ώ
IP 519 0-5VDC 2-60* 14-120 520Ώ
IP 520 0-10VDC 3-120* 20-830 825Ώ
* Output shows is as calinrated at at the factory. Large span adjustment capability allows recalibration to achieve output ranges from 20-240 kpa (3-35 psig) to 20-1000kpa (3-145 psig)