2/2-Way Pilot Operated, Diaphragm Type Solenoid Valves
Normally Closed, Energised To Open
Normally Open, Energised To Close
SPECIFICATIONS : |
Sizes |
10mm (3/8") to 75mm (3") |
End Connections |
Standard-BSP, Optional-NPT. |
Construction-Body |
Upto 20mm (3/4") Brass Forged IS 6912 and above in SS ASTM A351 Gr. CF8 Optional-SS ASTM A351 Gr.CF8M. |
Diaphragm Seat |
Standard-Nitrile (Buna 'N') Optional-Neoprene, Viton and other. |
Differential Pressure |
0.5 to 10 bar. |
Temperature of fluid |
-5°C to 120°C. |
Coil Voltage |
Standard-230-volts, 50Hz AC Optional-Any Standard AC/DC voltage range. |
Coil Insulation and Temperature |
Ambient upto 42 ° C. Class 'H' insulated upto 155° C, Class 'C' insulated upto 180° C. |
Coil Rating Enclosure |
Continuously rated. Standard-General Purpose SQ. moulded coil upto IP-20, Optional- Weatherproof SQ. moulded coil upto IP-67, Flameproof Round coil upto FLP IIB / IIC. |
Fluids |
Air, water, gas, light oil, heavy oil, mild corrosive fluid, etc |
SPECIFICATION TABLE
 2/2 WAY NORMALLY CLOSED
|
Catalogue Number |
pipe Size |
Orifice Size |
Flow Factor Kv |
Minimum pressure |
Maximum Operating Pressure (bar) |
BTP |
Material |
Constr. Ref. |
VA Rating |
Watt Rating |
Coil |
Housing |
A.C. |
D.C. |
Inch |
mm |
M³/hr. |
bar |
Air/Gas |
Water |
Light Oil |
Air/Gas |
Water |
Light Oil |
bar |
Body |
Seat |
AC |
DC |
Type |
9100F104 |
3/8 |
16 |
2.6 |
0.5 |
10 |
10 |
7 |
10 |
10 |
7 |
40 |
BR |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9100F154 |
1/2 |
16 |
3.4 |
0.5 |
10 |
10 |
7 |
10 |
10 |
7 |
40 |
BR |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9100F204 |
3/4 |
20 |
5.2 |
0.5 |
10 |
10 |
7 |
10 |
10 |
7 |
40 |
BR |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9100F254 |
1 |
25 |
8.6 |
0.5 |
10 |
10 |
7 |
10 |
10 |
7 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9100F304 |
1¼
|
28 |
14.0 |
0.5 |
10 |
10 |
6.5 |
10 |
10 |
7 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9100F354 |
1½
|
34 |
17.3 |
0.7 |
10 |
10 |
6.5 |
10 |
10 |
7 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9100F504 |
2 |
45 |
30.5 |
0.7 |
10 |
10 |
6 |
10 |
10 |
6 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9100F654 |
2½ |
60 |
45 |
0.7 |
10 |
10 |
8 |
10 |
10 |
8 |
40 |
CF8 |
BN |
153 |
36 |
22 |
M50 |
SQ |
9100F754 |
3 |
72 |
66 |
0.7 |
10 |
10 |
8 |
10 |
10 |
8 |
40 |
CF8 |
BN |
153 |
36 |
22 |
M50 |
SQ |
2/2 WAY NORMALLY OPEN (NEW MAGNETIC CONSTRUCTION TYPE) |
 |
9120F104 |
3/8 |
16 |
2.6 |
0.5 |
10 |
7 |
7 |
10 |
7 |
7 |
40 |
BR |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9120F154 |
1/2 |
16 |
3.4 |
0.5 |
10 |
7 |
7 |
10 |
7 |
7 |
40 |
BR |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9120F204 |
3/4 |
20 |
5.2 |
0.5 |
10 |
7 |
7 |
10 |
7 |
7 |
40 |
BR |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9120F254 |
1 |
25 |
8.6 |
0.5 |
10 |
7 |
7 |
10 |
7 |
6 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9120F304 |
1¼ |
28 |
14.0 |
0.5 |
10 |
7 |
7 |
10 |
7 |
6 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9120F354 |
1½ |
34 |
17.3 |
0.7 |
10 |
7 |
7 |
10 |
7 |
6 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9120F504 |
2 |
45 |
30.5 |
0.7 |
10 |
7 |
7 |
10 |
7 |
6 |
40 |
CF8 |
BN |
83.1 |
18 |
12 |
M45.1 |
SQ |
9120F654 |
2½ |
60 |
45 |
0.7 |
7 |
7 |
7 |
7 |
7 |
4 |
40 |
CF8 |
BN |
153 |
18 |
22 |
M50 |
SQ |
9120F754 |
3 |
72 |
66 |
0.7 |
7 |
7 |
7 |
7 |
7 |
4 |
40 |
CF8 |
BN |
153 |
18 |
22 |
M50 |
SQ |
|
|
ELECTRICAL REFERENCE |
Coil Type |
Power Consumption & Watt Rating |
Class of Insulation |
Protection |
AC |
DC |
VA Inrush |
VA Holding |
Watts |
M 45.1 SQ |
25 |
18 |
12 |
H |
C |
GP/WP IP-67 |
M 50 SQ |
50 |
36 |
22 |
H |
C |
GP/WP IP-67 |
M 45.1 RD |
25 |
18 |
12 |
H |
C |
GP/WP IP-67 |
M 50 RD |
50 |
36 |
22 |
H |
C |
GP/WP IP-67 |
M 45.1 FLP IIB / FLP IIC |
25 |
18 |
12 |
H |
C |
IS 2148 Group IIA, IIB, IIC IS 13947 Part I IP-67 IS 4012 Dustproof / IS 4013 Dusttight |
M 50 FLP IIB / FLP IIC |
50 |
36 |
22 |
H |
C |
|
|
|
|